Description:
Displays the reference quantity for power.
All power ratings specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency:
This value is calculated as follows:
Infeed: Calculated from voltage times current.
Closed-loop control: Calculated from torque times speed.
See also: p2000, p2001, p2002, p2003
Note
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
The reference power is calculated as follows:
- 2 * Pi * reference speed / 60 * reference torque (motor)
- reference voltage * reference current * root(3) (infeed)
p2006
Reference temperature / Ref temp
Access level: 3
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: 21_1
Unit selection: p0505
Function diagram: -
Min:
50.00 [°C]
Max:
300.00 [°C]
Factory setting:
100.00 [°C]
Description:
Sets the reference quantity for temperature.
All temperatures specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
p2010
Comm IF baud rate / Comm baud
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
6
Max:
12
Factory setting:
12
Description:
Sets the baud rate for the commissioning interface (USS, RS232).
Value:
6:
9600 baud
7:
19200 baud
8:
38400 baud
9:
57600 baud
10:
76800 baud
11:
93750 baud
12:
115200 baud
Note
COMM-IF: Commissioning interface
The parameter is not influenced by setting the factory setting.
p2011
Comm IF address / Comm add
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
31
Factory setting:
2
Description:
Sets the address for the commissioning interface (USS, RS232).
Parameters