Number
Name
p9400
Safely remove memory card / Mem_card rem
p9484
BICO interconnections search signal source / BICO S_src srch
Note
Write protection for multimaster fieldbus systems
Via multimaster fieldbus systems, e.g. BACnet or Modbus RTU, in spite of write protection
being activated, parameters can still be changed. So that write protection is also active when
accessing via these fieldbuses, you must additionally set p7762 to 1.
Saving the settings and series commissioning
8.5 Write protection
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
737