r1526
CO: Torque limit upper without offset / M_max up w/o offs
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2003
Dynamic index: -
Unit group: 7_1
Unit selection: p0505
Function diagram: 6060, 6630,
6640
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description:
Display and connector output for the upper torque limit of all torque limits without offset.
Dependency:
See also: p1520, p1521, p1522, p1523
r1527
CO: Torque limit lower without offset / M_max low w/o offs
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2003
Dynamic index: -
Unit group: 7_1
Unit selection: p0505
Function diagram: 6060, 6630,
6640
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description:
Display and connector output for the lower torque limit of all torque limits without offset.
Dependency:
See also: p1520, p1521, p1522, p1523
p1530[0...n]
Power limit motoring / P_max mot
Access level: 2
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 14_5
Unit selection: p0505
Function diagram: 6640
Min:
0.00 [kW]
Max:
100000.00 [kW]
Factory setting:
0.00 [kW]
Description:
Sets the power limit when motoring.
Dependency:
See also: p0500, p1531
Note
The power limit is limited to 300% of the rated motor power.
p1531[0...n]
Power limit regenerative / P_max gen
Access level: 2
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 14_5
Unit selection: p0505
Function diagram: 6640
Min:
-100000.00 [kW]
Max:
-0.01 [kW]
Factory setting:
-0.01 [kW]
Description:
Sets the regenerative power limit.
Dependency:
See also: r0206, p0500, p1530
Note
The power limit is limited to 300% of the rated motor power.
For power units without energy recovery capability, the regenerative power limit is preset to 30 % of the power r0206[0].
For power units with energy recovery, the parameter is limited to the negative value of r0206[2].
Parameters
7.3 Parameters
SINAMICS G120XA converter
526
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB