Index:
[0] = Unsmoothed
[1] = Smoothed
Dependency:
See also: p0341, p0342, p1496
p1520[0...n]
CO: Torque limit upper / M_max upper
Access level: 2
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2003
Dynamic index: DDS, p0180
Unit group: 7_1
Unit selection: p0505
Function diagram: 6020, 6630
Min:
-1000000.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
0.00 [Nm]
Description:
Sets the fixed, upper torque limit.
Dependency:
See also: p1521, p1522, p1523, r1538, r1539
DANGER
Negative values when setting the upper torque limit (p1520 < 0) can result in the motor accelerating in an
uncontrollable fashion.
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
The torque limit is limited to 400% of the rated motor torque. When automatically calculating the motor/closed-loop
control parameters (p0340), the torque limit is set to match the current limit (p0640).
p1521[0...n]
CO: Torque limit lower / M_max lower
Access level: 2
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2003
Dynamic index: DDS, p0180
Unit group: 7_1
Unit selection: p0505
Function diagram: 6020, 6630
Min:
-20000000.00 [Nm]
Max:
1000000.00 [Nm]
Factory setting:
0.00 [Nm]
Description:
Sets the fixed, lower torque limit.
Dependency:
See also: p1520, p1522, p1523
DANGER
Positive values when setting the lower torque limit (p1521 > 0) can result in the motor accelerating in an uncontrollable
fashion.
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
The torque limit is limited to 400% of the rated motor torque. When automatically calculating the motor/closed-loop
control parameters (p0340), the torque limit is set to match the current limit (p0640).
p1522[0...n]
CI: Torque limit upper / M_max upper
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: p2003
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 6630
Min:
-
Max:
-
Factory setting:
1520[0]
Description:
Sets the signal source for the upper torque limit.
Parameters
7.3 Parameters
SINAMICS G120XA converter
524
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Summary of Contents for SINAMICS G120XA
Page 2: ......
Page 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Page 917: ......