Table 3-2
FSH and FSJ
Drill pattern
Dimensions
FSH
FSJ
*
$
$
$
*
$
$
%
A1
150
247
A2
150
200
A3
150
200
A4
225
367
A5
225
315
B
1444
1399
G1
49
61
G2
49
60
Ø
20
20
Fixings (bolts, wash‐
ers, nuts)
7 × M8
7 × M8
Tightening torque (Nm) 25
25
3.3.3
Mounting the shield connection kit
Overview
We recommend that you mount the shield connection kits provided. The shield connection kit
makes it simpler to install the converter in compliance with EMC regulations and to provide
strength relief for the connected cables.
Mounting the shield connection kit for the Control Unit
Note
The shield connection kit for the Control Unit is available for converters FSD to FSG only.
Attach the shielding plate to the bottom of the Control Unit, and use a cross-tip screwdriver to
tighten the screw to fix it onto the converter.
Mounting
3.3 Mounting the converter
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
49