r0047
Motor data identification and speed controller optimization / MotID and n_opt
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
300
Factory setting:
-
Description:
Displays the actual status for the motor data identification (stationary measurement) and the speed controller
optimization (rotating measurement).
Value:
0:
No measurement
115:
Measurement q leakage inductance (part 2)
120:
Speed controller optimization (vibration test)
140:
Calculate speed controller setting
150:
Measurement moment of inertia
170:
Measurement magnetizing current and saturation characteristic
195:
Measurement q leakage inductance (part 1)
200:
Rotating measurement selected
220:
identification leakage inductance
230:
Identification rotor time constant
240:
Identification stator inductance
250:
Identification stator inductance LQLD
260:
Identification circuit
270:
Identification stator resistance
290:
Identification valve lockout time
300:
Stationary measurement selected
r0047
Motor data identification and speed controller optimization / MotID and n_opt
CUG120XA_USS
(PM330)
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
300
Factory setting:
-
Description:
Displays the actual status for the motor data identification (stationary measurement) and the speed controller
optimization (rotating measurement).
Value:
0:
No measurement
115:
Measurement q leakage inductance (part 2)
120:
Speed controller optimization (vibration test)
140:
Calculate speed controller setting
150:
Measurement moment of inertia
170:
Measurement magnetizing current and saturation characteristic
195:
Measurement q leakage inductance (part 1)
200:
Rotating measurement selected
220:
identification leakage inductance
230:
Identification rotor time constant
240:
Identification stator inductance
250:
Identification stator inductance LQLD
270:
Identification stator resistance
290:
Identification valve lockout time
295:
Calibration output voltage measurement
300:
Stationary measurement selected
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
363