Example
'2
U
S
To output converter fault messages via digital output DO 1, you must interconnect DO 1 with
these fault messages.
Set p0731 = 52.3
Parameters
Table 6-3
Frequently used binector outputs (BO) of the converter
Parameter
Description
Factory setting
r0052[0...15] CO/BO: Status word 1
-
.00
1 signal: Ready for switching on
.01
1 signal: Ready for operation
.02
1 signal: Operation enabled
.03
1 signal: Fault active: The converter inverts signal
r0052.03 if it is interconnected to a digital output.
.04
0 signal: OFF2 active
.05
0 signal: OFF3 active
.06
1 signal: Switching on inhibited active
.07
1 signal: Alarm active
.08
0 signal: Deviation, setpoint/actual speed
.09
1 signal: Control request
.10
1 signal: Maximum speed (p1082) reached
.11
0 signal: I, M, P limit reached
.13
0 signal: Alarm, motor overtemperature
.14
1 signal: Motor clockwise rotation
.15
0 signal: Alarm, converter overload
r0053[0...11] CO/BO: Status word 2
-
.00
1 signal: DC braking active
.02
1 signal: Speed > minimum speed (p1080)
.06
1 signal: Speed ≥ setpoint speed (r1119)
You can find additional binector outputs in the parameter list.
See also
Interconnecting signals in the converter (Page 882)
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
138
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB