6.2.2.1
Digital inputs
Function description
',
',
',
',
',
',
U
U
U
U
U
U
%,S[[[[
To change the function of a digital input, you must interconnect the status parameter of the
digital input with a binector input of your choice.
Binector inputs are designated in the parameter list with the prefix “BI:".
Example
',
U
S
To acknowledge converter fault messages using digital input DI 1, you must interconnect DI 1
with the command to acknowledge faults (p2103).
Set p2103 = 722.1.
Parameters
Parameter
Description
Factory setting
r0721
CU digital inputs, terminal actual value
-
r0722
CO/BO: CU digital inputs, status
-
r0723
CO/BO: CU digital inputs, status inverted
--
p0724
CU digital inputs debounce time
4 ms
p0810
BI: Command data set selection CDS bit 0
0
p0840[C]
BI: ON/OFF (OFF1)
Dependent on the converter
p0844[C]
BI: No coast down/coast down (OFF2) signal
source 1
Dependent on the converter
p0848[C]
BI: No quick stop/quick stop (OFF3) signal source
1
1
p0852[C]
BI: Enable operation/inhibit operation
Dependent on the converter
p1020[C]
BI: Fixed speed setpoint selection, bit 0
0
p1021[C]
BI: Fixed speed setpoint selection, bit 1
0
p1022[C]
BI: Fixed speed setpoint selection, bit 2
0
p1023[C]
BI: Fixed speed setpoint selection, bit 3
0
p1035[C]
BI: Motorized potentiometer setpoint higher
Dependent on the converter
p1036[C]
BI: Motorized potentiometer setpoint lower
Dependent on the converter
p1055[C]
BI: Jogging bit 0
Dependent on the converter
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
131