Description:
Sets the second signal source for the command "No quick stop/quick stop (OFF3)".
The following signals are AND'ed:
- BI: p0848 "No quick stop / quick stop (OFF3) signal source 1"
- BI: p0849 "No quick stop / quick stop (OFF3) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 2 (STW1.2).
BI: p0848 = 0 signal or BI: p0849 = 0 signal
- OFF3 (braking along the OFF3 ramp (p1135), then pulse suppression and switching on inhibited)
BI: p0848 = 1 signal and BI: p0849 = 1 signal
- no OFF3 (enable is possible)
CAUTION
When "master control from PC" is activated, this binector input is effective.
p0852[0...n]
BI: Enable operation/inhibit operation / Enable operation
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2501
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for the command "enable operation/inhibit operation".
For the PROFIdrive profile, this command corresponds to control word 1 bit 3 (STW1.3).
BI: p0852 = 0 signal
Inhibit operation (suppress pulses).
BI: p0852 = 1 signal
Enable operation (pulses can be enabled).
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0854[0...n]
BI: Control by PLC/no control by PLC / Master ctrl by PLC
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2501
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for the command "control by PLC/no control by PLC".
For the PROFIdrive profile, this command corresponds to control word 1 bit 10 (STW1.10).
BI: p0854 = 0 signal
No control by PLC
BI: p0854 = 1 signal
Master control by PLC.
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.