00
DI 0 (X133. 5)
High
Low
-
01
DI 1 (X133. 6)
High
Low
-
02
DI 2 (X133. 7)
High
Low
-
03
DI 3 (X133. 8)
High
Low
-
04
DI 4 (X133. 16)
High
Low
-
05
DI 5 (X133. 17)
High
Low
-
11
DI 11 (X131. 3, 4) AI 0
High
Low
-
12
DI 12 (X131. 10, 11) AI 1
High
Low
-
Dependency:
See also: r0723
Note
AI: Analog Input
DI: Digital Input
r0723.0...12
CO/BO: CU digital inputs status inverted / CU DI status inv
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2119, 2120,
2121, 2130, 2131, 2132, 2133
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the inverted status of the digital inputs.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI 0 (X133. 5)
High
Low
-
01
DI 1 (X133. 6)
High
Low
-
02
DI 2 (X133. 7)
High
Low
-
03
DI 3 (X133. 8)
High
Low
-
04
DI 4 (X133. 16)
High
Low
-
05
DI 5 (X133. 17)
High
Low
-
11
DI 11 (X131. 3, 4) AI 0
High
Low
-
12
DI 12 (X131. 10, 11) AI 1
High
Low
-
Dependency:
See also: r0722
Note
AI: Analog Input
DI: Digital Input
p0724
CU digital inputs debounce time / CU DI t_debounce
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.000 [ms]
Max:
20.000 [ms]
Factory setting:
4.000 [ms]
Description:
Sets the debounce time for digital inputs.
Note
The digital inputs are read in cyclically every 2 ms (DI 11, DI 12 every 4 ms).
To debounce the signals, the set debounce time is converted into integer multiple debounce clock cycles Tp (Tp =
p0724 / 2 ms).
DI: Digital Input
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
427