F07950 (A)
Motor parameter incorrect
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The motor parameters were incorrectly entered while commissioning (e.g. p0300 = 0, no motor)
Fault value (r0949, interpret decimal):
Parameter number involved.
See also: p0300, p0301, p0304, p0305, p0307, p0310, p0311, p0314, p0315, p0316, p0320, p0322, p0323
Remedy:
Compare the motor data with the rating plate data and if required, correct.
F07967
Drive: Incorrect pole position identification
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
A fault has occurred during the pole position identification routine.
Only for internal Siemens troubleshooting.
Remedy:
Carry out a POWER ON.
F07968
Drive: Lq-Ld measurement incorrect
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A fault has occurred during the Lq-Ld measurement.
Fault value (r0949, interpret decimal):
10: Stage 1: The ratio between the measured current and zero current is too low.
12: Stage 1: The maximum current was exceeded.
15: Second harmonic too low.
16: Drive converter too small for the measuring technique.
17: Abort due to pulse inhibit.
Remedy:
For fault value = 10:
Check whether the motor is correctly connected.
Replace the power unit involved.
Deactivate technique (p1909).
For fault value = 12:
Check whether motor data have been correctly entered.
Deactivate technique (p1909).
For fault value = 16:
Deactivate technique (p1909).
For fault value = 17:
Repeat technique.
F07969
Drive: Incorrect pole position identification
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Warnings, faults and system messages
9.6 List of fault codes and alarm codes
SINAMICS G120XA converter
798
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB