r0837.0...1
CO/BO: Drive Data Set DDS selected / DDS selected
Access level: 3
Calculated: -
Data type: Unsigned8
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8565
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the drive data set (DDS) selected via the binector input.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DDS selection bit 0
ON
OFF
-
01
DDS selection bit 1
ON
OFF
-
Dependency:
See also: r0051, p0820, p0821
Note
Drive data sets are selected via binector input p0820 and following.
The currently effective drive data set is displayed in r0051.
If there is only one data set, then a value of 0 is displayed in this parameter and not the selection via binector inputs.
p0840[0...n]
BI: ON / OFF (OFF1) / ON / OFF (OFF1)
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2501, 2512
Min:
-
Max:
-
Factory setting:
[0] 29659.0
[1] 0
[2] 0
[3] 0
Description:
Sets the signal source for the command "ON/OFF (OFF1)".
For the PROFIdrive profile, this command corresponds to control word 1 bit 0 (STW1.0).
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
See also: p1055, p1056
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
For binector input p0840 = 0 signal, the motor can be moved, jogging using binector input p1055 or p1056.
The command "ON/OFF (OFF1)" can be issued using binector input p0840 or p1055/p1056.
For binector input p0840 = 0 signal, the switching on inhibited is acknowledged.
Only the signal source that originally switched on can also switch off again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0844[0...n]
BI: No coast-down / coast-down (OFF2) signal source 1 / OFF2 S_src 1
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2501, 8720,
8820, 8920
Min:
-
Max:
-
Factory setting:
[0] 29659.1
[1] 1
[2] 1
[3] 1
Parameters
7.3 Parameters
SINAMICS G120XA converter
448
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB