Note
To permanently accept the determined settings they must be saved in a non-volatile fashion (p0971).
When setting p1910, the following should be observed:
1. "With acceptance" means:
The parameters specified in the description are overwritten with the identified values and therefore have an influence
on the controller setting.
2. "Without acceptance" means:
The identified parameters are only displayed in the range r1912 ... r1926 (service parameters). The controller settings
remain unchanged.
3. For settings 27 and 28, the AVC configuration set using p1840 is active.
The switch-on command must remain set during a measurement and after the measurement has been completed, the
drive automatically resets it. The duration of the measurements can lie between 0.3 s and several minutes. This time
is mainly influenced by the motor size. At the end of the motor data identification, p1910 is automatically set to 0, if only
the stationary measurement is selected, then p1900 is also reset to 0, otherwise, the rotating measurement is activated.
p1959[0...n]
Rotating measurement configuration / Rot meas config
Access level: 3
Calculated: CALC_MOD_ALL Data type: Unsigned16
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 0000 0001 1110 bin
Description:
Sets the configuration of the rotating measurement.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
Saturation characteristic identification
Yes
No
-
02
Moment of inertia identification
Yes
No
-
03
Re-calculates the speed controller parameters
Yes
No
-
04
Speed controller optimization (vibration test)
Yes
No
-
11
Do not change the controller parameters during the
measurement
Yes
No
-
12
Measurement shortened
Yes
No
-
13
After measurement direct transition into operation
Yes
No
-
14
Calculate speed actual value smoothing time
Yes
No
-
Dependency:
See also: F07988
Note
The following parameters are influenced for the individual optimization steps:
Bit 01: p0320, p0360, p0362 ... p0369
Bit 02: p0341, p0342
Bit 03: p1400.0, p1458, p1459, p1463, p1470, p1472, p1496
Bit 04: Dependent on p1960
p1960 = 1, 3: p1400.0, p1458, p1459, p1470, p1472, p1496
p1959[0...n]
Rotating measurement configuration / Rot meas config
CUG120XA_USS
(PM330)
Access level: 3
Calculated: CALC_MOD_ALL Data type: Unsigned16
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0001 0000 0001 1110 bin
Description:
Sets the configuration of the rotating measurement.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
Saturation characteristic identification
Yes
No
-
02
Moment of inertia identification
Yes
No
-
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
547