Parameter
Description
Factory setting
p2382
Cascade control absolute operating time limit
24 h
p2383
Cascade control deactivation sequence
0
p2384
Cascade control motor switch-on delay
0 s
p2385
Cascade control stop time activation speed
0 s
p2386
Cascade control motor switch-off delay
0 s
p2387
Cascade control stop time deactivation speed
0 s
Additional information is provided in the parameter list and in function diagram 7036.
Further information
Interaction with the "Hibernation mode" function
In order that the "Cascade control" and "Hibernation mode" functions do not influence each
other, you must make the following settings in the cascade control:
● p2392 < p2373
The restart value of the hibernation mode p2392 must be lower than the activation threshold
for the cascade control p2373.
● p2373 < p2376
The activation threshold for the cascade control p2373 must be lower than the overload
threshold for the cascade control p2376.
● It is not permissible for the main drive to be in the hibernation mode.
● The actual speed must be higher than the restart speed for hibernation mode
(p1080 + p2390) × 1.05.
● The value for the activation delay of the cascade control p2374 must be higher than the
ramp-up time t
y
from hibernation mode.
t
y
= (p1080 + p2390) × 1.05 × p1120 × p1139/p1082
Advanced commissioning
6.5 Technology controller
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
269