p0868
Power unit thyristor rectifier wait time / PU thy_rect t
CUG120XA_USS
(PM330)
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [ms]
Max:
65000 [ms]
Factory setting:
0 [ms]
Description:
Sets the debounce time for the DC circuit breaker for power units in the "chassis" format.
Dependency:
The parameter is only active for PM330 power units.
Note
The following applies if p0868 = 65000 ms:
The debounce time defined internally in the power unit's EEPROM is implemented.
p0869
Sequence control configuration / Seq_ctrl config
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description:
Sets the configuration for the sequence control.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Keep main contactor closed for STO
Yes
No
-
Dependency:
See also: p0867
Note
For bit 00:
After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869.0 = 1, after withdrawing STO, the switching on inhibited must be acknowledged via the source of p0840 =
0 (OFF1) – and before the main contactor holding time expires (p0867), should go back to 1, otherwise the main
contactor will open.
p0870
BI: Close main contactor / Close main cont
Access level: 2
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to close the main contactor.
Note
The main contactor is also closed when the converter is switched on after issuing the necessary enable signals. A
binector input p0870 = 1 signal prevents the main contactor from being opened when enable signals are withdrawn.
r0898.0...10
CO/BO: Control word sequence control / STW seq_ctrl
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2501
Min:
-
Max:
-
Factory setting:
-
Description:
Display and connector output for the control word of the sequence control.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
Parameters
7.3 Parameters
SINAMICS G120XA converter
454
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Summary of Contents for SINAMICS G120XA
Page 2: ......
Page 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Page 917: ......