p1144[0...n]
CI: Ramp-function generator setting value / RFG setting value
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
-
Max:
-
Factory setting:
29641[0]
Description:
Sets the signal source for the ramp-function generator setting value.
Dependency:
The signal source for accepting the setting value is set using parameters.
See also: p1143
p1148[0...n]
Ramp-function gen. tolerance for ramp-up and ramp-down active / RFG tol HL/RL act
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3070
Min:
0.000 [rpm]
Max:
1000.000 [rpm]
Factory setting:
19.800 [rpm]
Description:
Sets the tolerance value for the status of the ramp-function generator (ramp-up active, ramp-down active).
If the input of the ramp-function generator does not change in comparison to the output by more than the entered
tolerance time, then the status bits "ramp-up active" and "ramp-down active" are not influenced.
r1149
CO: Ramp-function generator acceleration / RFG acceleration
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2007
Dynamic index: -
Unit group: 39_1
Unit selection: p0505
Function diagram: 3070
Min:
- [rev/s²]
Max:
- [rev/s²]
Factory setting:
- [rev/s²]
Description:
Displays the acceleration of the ramp-function generator.
r1170
CO: Speed controller setpoint sum / Speed setpoint sum
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 3001, 3080,
6300
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Display and connector output for the speed setpoint after selecting the ramp-function generator.
The value is the sum of speed setpoint 1 (p1155) and speed setpoint 2 (p1160).
r1198.0...15
CO/BO: Control word setpoint channel / STW setpoint chan
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2505
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the control word of the setpoint channel.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fixed setpoint bit 0
Yes
No
3010
01
Fixed setpoint bit 1
Yes
No
3010
Parameters
7.3 Parameters
SINAMICS G120XA converter
488
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB