Description:
Displays the remaining time after activating the "DC link capacitor forming" function.
Dependency:
See also: p3380, r3382
r3382
Forming status word / Forming ZSW
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status word of the "DC link capacitor forming" function.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Forming activated
Yes
No
-
01
Forming active
Yes
No
-
02
Forming completed
Yes
No
-
03
Forming fault
Yes
No
-
Dependency:
See also: p3380, r3381
See also: F07390, A07391
Note
For bit 00 = 1:
The parameter for activation/duration has been set (p3380 > 0) - however, forming has still not been started (p0840 =
0 signal).
For bit 01 = 1:
The parameter for activation/duration has been set (p3380 > 0) - however, forming has still not been started (p0840 =
0/1 signal).
This status is displayed through alarm A07391.
The procedure can be interrupted via binector input p0840, p0844, p0848 (r3382.1 = 0) - and reactivated again using
p0840.
For bit 03 = 1:
Forming was not able to be successfully performed within the set duration.
This status is displayed using fault F07390.
p3855[0...n]
DC quantity controller configuration / Rect_ctrl config
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: Unsigned32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6797, 6844,
6855
Min:
-
Max:
-
Factory setting:
0111 bin
Description:
Sets the configuration for the DC quantity controller in the overmodulation range.
There is no DC quantity control for power units that can also be connected through 1 phase to the line supply (r0204.15
= 1).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DC quantity controller on
Yes
No
-
01
Bandwidth increased
Yes
No
-
02
7th harmonic reduced
Yes
No
-
03
Filter active
Yes
No
-
Dependency:
The modulator mode p1802 must enable operation in the overmodulation range. In addition, the overmodulation limit
p1803 must be greater than 103 %.
Set the modulator mode p1802 = 10, if the DC quantity control is deactivated and overmodulation is to be prevented.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
651