06
Speed controller I component set
Yes
No
6040
07
Torque limit reached
Yes
No
6060
08
Upper torque limit active
Yes
No
6060
09
Lower torque limit active
Yes
No
6060
10
Reserved
-
-
-
11
Speed setpoint limited
Yes
No
6030
12
Ramp-function generator set
Yes
No
-
13
Encoderless operation due to a fault
Yes
No
-
14
I/f control active
Yes
No
-
15
Torque limit reached (without precontrol)
Yes
No
6060
17
Speed limiting control active
Yes
No
6640
23
Acceleration model activated
Yes
No
-
r1438
CO: Speed controller speed setpoint / n_ctrl n_set
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 3001, 6020,
6031
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Display and connector output of the speed setpoint after setpoint limiting for the P component of the speed controller.
For U/f operation, the value that is displayed is of no relevance.
Note
In the standard state (the reference model is deactivated), r1438 = r1439.
p1452[0...n]
Speed controller speed actual value smoothing time (sensorless) / n_C n_act T_s SL
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6020, 6040
Min:
0.00 [ms]
Max:
32000.00 [ms]
Factory setting:
10.00 [ms]
Description:
Sets the smoothing time for the actual speed of the speed controller for encoderless closed-loop speed control.
Note
The smoothing must be increased if there is gear backlash. For longer smoothing times, the integral time of the speed
controller must also be increased (e.g. using p0340 = 4).
p1461[0...n]
Speed controller Kp adaptation speed upper scaling / n_ctr Kp n up scal
Access level: 3
Calculated: CALC_MOD_CON Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6050
Min:
0.0 [%]
Max:
200000.0 [%]
Factory setting:
100.0 [%]
Description:
Sets the P gain of the speed controller for the upper adaptation speed range (> p1465).
The entry is made referred to the P gain for the lower adaptation speed range of the speed controller (% referred to
p1470).
Dependency:
See also: p1464, p1465
Parameters
7.3 Parameters
SINAMICS G120XA converter
520
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Summary of Contents for SINAMICS G120XA
Page 2: ......
Page 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Page 917: ......