Description:
Display and connector output for the field-generating current setpoint (Id_set).
Note
This value is irrelevant for the U/f control mode.
r0076
CO: Current actual value field-generating / Id_act
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2002
Dynamic index: -
Unit group: 6_2
Unit selection: p0505
Function diagram: 5700, 5714,
5730, 6700, 6714, 6799
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description:
Display and connector output for the field-generating current actual value (Id_act).
Note
This value is irrelevant for the U/f control mode.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
r0077
CO: Current setpoint torque-generating / Iq_set
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2002
Dynamic index: -
Unit group: 6_2
Unit selection: p0505
Function diagram: 6700, 6710
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description:
Display and connector output for the torque-generating current setpoint.
Note
This value is irrelevant for the U/f control mode.
r0078
CO: Current actual value torque-generating / Iq_act
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2002
Dynamic index: -
Unit group: 6_2
Unit selection: p0505
Function diagram: 6310, 6700,
6714, 6799
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description:
Display and connector output for the torque-generating current actual value (Iq_act).
Note
This value is irrelevant for the U/f control mode.
The torque-generating current actual value is available smoothed (r0030 with 300 ms) and unsmoothed (r0078).
r0079
CO: Torque setpoint / M_set
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2003
Dynamic index: -
Unit group: 7_1
Unit selection: p0505
Function diagram: 6020, 6060,
6710
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description:
Display and connector output for the torque setpoint at the output of the speed controller.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
373