Index:
[0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency:
See also: p8409, p8410, r8413
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8412[0...1]
RTC DTC1 off time / RTC DTC1 t_OFF
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
59
Factory setting:
0
Description:
Sets the switch-off time in hours and minutes for time switch 1 (DTC1).
BO: r8413 = 0 signal:
The condition for the set weekday (p8410) and switch-off time has been fulfilled.
Index:
[0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency:
See also: p8409, p8410, r8413
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
r8413.0...1
BO: RTC DTC1 output / RTC DTC1 output
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Display and binector output for the output of time switch 1 (DTC1).
Where a weekday is deactivated, the following applies (p8410):
- the binector output for this timer is inactive (r8413.0 = 0).
Where a weekday is activated, the following applies (p8410):
- the ON/OFF time setting (p8411, p8412) for this timer has an instant effect on the binector output (r8413).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Timer on
Yes
No
-
01
Timer ON negated
No
Yes
-
Dependency:
See also: p8409, p8410, p8411, p8412
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
675