NOTICE
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1058[0...n]
Jog 1 speed setpoint / Jog 1 n_set
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3001, 3030
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
150.000 [rpm]
Description:
Sets the speed for jog 1.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency:
See also: p1055, p1056
p1059[0...n]
Jog 2 speed setpoint / Jog 2 n_set
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3001, 3030
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
-150.000 [rpm]
Description:
Sets the speed for jog 2.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency:
See also: p1055, p1056
p1063[0...n]
Setpoint channel speed limit / Setp_chan n_lim
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3040
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
210000.000 [rpm]
Description:
Sets the speed limit effective in the setpoint channel.
Dependency:
See also: p1082, p1083, p1085, p1086, p1088
p1070[0...n]
CI: Main setpoint / Main setpoint
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: p2000
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3001, 3030
Min:
-
Max:
-
Factory setting:
[0] 755[0]
[1] 0
[2] 0
[3] 0
Description:
Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency:
See also: p1071, r1073, r1078
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
473