p11253
CI: Free tec_ctrl 2 setpoint signal source / Ftec2 setp s_src
Access level: 2
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the setpoint of the free technology controller 2.
p11257
Free tec_ctrl 2 setpoint ramp-up time / Ftec2 setp t_r-up
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0.00 [s]
Max:
650.00 [s]
Factory setting:
1.00 [s]
Description:
Sets the ramp-up time for the free technology controller 2.
Dependency:
See also: p11258
Note
The ramp-up time is referred to 100 %.
p11258
Free tec_ctrl 2 setpoint ramp-down time / Ftec2 setp t_r-dn
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0.00 [s]
Max:
650.00 [s]
Factory setting:
1.00 [s]
Description:
Sets the ramp-down time of the free technology controller 2.
Dependency:
See also: p11257
Note
The ramp-down time is referred to 100 %.
r11260
CO: Free tec_ctrl 2 setpoint after ramp-function generator / Ftec2 setp aft RFG
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: PERCENT
Dynamic index: -
Unit group: 9_4
Unit selection: p11226
Function diagram: 7030
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Display and connector output for the setpoint after the ramp-function generator of the free technology controller 2.
p11263
Free tec_ctrl 2 system deviation inversion / Ftec2 sys_dev inv
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0
Max:
1
Factory setting:
0
Description:
Sets the inversion of the system deviation of the free technology controller 2.
The setting depends on the type of control loop.
Value:
0:
No inversion
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
701