2.6
Optional components
2.6.1
Overview
The following optional components are available so that you can adapt the converter to different
applications and ambient conditions:
● Overview (Page 31)
● Output reactor (Page 32)
● Sine-wave filter (Page 34)
● dv/dt filter plus VPL (Page 35)
● Operator panel (Page 35)
● SINAMICS G120 Smart Access (Page 36)
● Shield connection kit for the Power Module (FSD to FSG) (Page 36)
Further information
Further information about the technical specifications and installing of these optional
components is described in the documentation provided.
Note
Line reactors are not required for converters of frame sizes FSA to FSG.
A line reactor is needed for high short-circuit power levels, partly to protect the actual converter
against excessive harmonic currents, and thus against overload, and partly to limit line
harmonics to the permitted values. The harmonic currents are limited by the total inductance
comprising the line reactor and mains supply cable inductance. Line reactors can be omitted if
the mains supply cable inductance is increased sufficiently, i.e., the value of R
SC
must be
sufficiently small.
R
SC
= Relative Short-Circuit power: ratio of short-circuit power S
k Line
at the supply connection
point to the fundamental apparent power S
inv
of the connected converters (to IEC 60146-1-1).
0DLQVXSSO\FDEOH
LQGXFWDQFH
&RQQHFWLRQSRLQWRI
WKHFRQYHUWHU
&RQYHUWHU
/LQHUHDFWRU
/LQH
6
NOLQH
Description
2.6 Optional components
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
31
Summary of Contents for SINAMICS G120XA
Page 2: ......
Page 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Page 917: ......