p11153
CI: Free tec_ctrl 1 setpoint signal source / Ftec1 setp s_s
Access level: 2
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the setpoint of the free technology controller 1.
p11157
Free tec_ctrl 1 setpoint ramp-up time / Ftec1 setp t_r-up
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0.00 [s]
Max:
650.00 [s]
Factory setting:
1.00 [s]
Description:
Sets the ramp-up time for the free technology controller 1.
Dependency:
See also: p11158
Note
The ramp-up time is referred to 100 %.
p11158
Free tec_ctrl 1 setpoint ramp-down time / Ftec1 setp t_r-dn
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0.00 [s]
Max:
650.00 [s]
Factory setting:
1.00 [s]
Description:
Sets the ramp-down time of the free technology controller 1.
Dependency:
See also: p11157
Note
The ramp-down time is referred to 100 %.
r11160
CO: Free tec_ctrl 1 setpoint after ramp-function generator / Ftec1 setp aft RFG
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: PERCENT
Dynamic index: -
Unit group: 9_3
Unit selection: p11126
Function diagram: 7030
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Display and connector output for the setpoint after the ramp-function generator of the free technology controller 1.
p11163
Free tec_ctrl 1 system deviation inversion / Ftec1 sys_dev inv
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0
Max:
1
Factory setting:
0
Description:
Sets the inversion of the system deviation of the free technology controller 1.
The setting depends on the type of control loop.
Value:
0:
No inversion
Parameters
7.3 Parameters
SINAMICS G120XA converter
694
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Summary of Contents for SINAMICS G120XA
Page 2: ......
Page 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Page 917: ......