Parameters
Number
Name
Factory setting
p29522
Multi-pump control motor selection mode
0
r29529.6
CO/BO: Multi-pump control status word: pump switchover is
not possible
-
p29530[0...3]
Multi-pump control motors absolute operating hours
-
p29531
Multi-pump control maximum time for continuous operation
24 h
p29539
Multi-pump control switchover enable
0
p29547[0...3]
Multi-pump control motors continuous operating hours
-
r29538
Multi-pump control variable-speed motor
-
For more information about the parameters, see Chapter "Parameters (Page 349)".
6.3.1.4
Service mode
Function description
When a pump is in service mode, the converter locks the corresponding relay. Then you can
perform troubleshooting of this pump without interrupting the operation of other pumps. You
can use parameters p29540 to p29543 to set the pumps to work in service mode respectively.
Pumps in service mode are skipped in further multi-pump control process.
WARNING
Risk of electric shock due to incorrectly connected low-voltage circuit breakers
If a low-voltage circuit breaker is not connected correctly to a pump set in service mode,
hazardous voltages can be present at the pump when the converter relay malfunctions.
Troubleshooting the service pump can result in serious personal injury or death.
● Make sure that all pumps are connected correctly to the mains and converter through low-
voltage circuit breakers.
● After a pump is set in service mode, make sure that its low-voltage circuit breaker is open
before performing any troubleshooting operation.
SS
%LW
%LW
%LW
%LW
'LVSOD\VZKLFKPRWRULV
FRQWUROOHGE\WKHLQYHUWHU
/RFNVPRWRU
PDQXDOO\
'LJLWDOLQSXWV
6LJQDOVRXUFH
6HUYLFHPRGHVWDWXVRIPRWRUV
(QDEOHVVHUYLFHPRGH
U
U
U
U
U
U
U
S
S
S
Advanced commissioning
6.3 Pump control
SINAMICS G120XA converter
212
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Summary of Contents for SINAMICS G120XA
Page 2: ......
Page 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Page 917: ......