Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
r8433.0...1
BO: RTC DTC3 output / RTC DTC3 output
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Display and binector output for the output of timer 3 (DTC3).
Where a weekday is deactivated, the following applies (p8430):
- the binector output for this timer is inactive (r8433.0 = 0).
Where a weekday is activated, the following applies (p8430):
- the ON/OFF time setting (p8431, p8432) for this timer has an instant effect on the binector output (r8433).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Timer on
Yes
No
-
01
Timer ON negated
No
Yes
-
Dependency:
See also: p8409, p8430, p8431, p8432
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
r8540.0...15
BO: STW1 from IOP in the manual mode / STW1 IOP
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
For the manual mode: the STW1 (control word 1) entered from the IOP is displayed.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON/OFF1
Yes
No
-
01
OC / OFF2
Yes
No
-
02
OC / OFF3
Yes
No
-
03
Reserved
Yes
No
-
04
Reserved
Yes
No
-
05
Reserved
Yes
No
-
06
Reserved
Yes
No
-
07
Acknowledge fault
Yes
No
-
08
Jog bit 0
Yes
No
3030
09
Jog bit 1
Yes
No
3030
10
Reserved
Yes
No
-
11
Direction reversal (setpoint)
Yes
No
-
12
Reserved
Yes
No
-
13
Reserved
Yes
No
-
14
Reserved
Yes
No
-