CHAPTER 3.0 Wiring and Installation
3-25
CDS7324 (FORMERLY LSF-0819)
Rev. A
INSTALLATION & USER’S MANUAL
3.7.1.2
Size A & B
EMC Filter,
Fuses etc.
See
Section 2
Installation
4 5 6
U1 V1 W1
Connector J6
Α & Β
PE
Stud
a.c. Mains
L1
L2
L3
Protective
Earth
Figure 3.18 A & B AC Mains Input Connection
-
Fixed connector: 12 pins, male connector
-
Mating connector, 12 pins, female, supplied with the drive. Phoenix Contact (Part # 1767106)
-
A size wiring: cable 14AWG (2.1 mm
2
). Wire stripping: 7 mm
-
B size wiring: cable 12AWG (3.3 mm
2
). Wire stripping: 7 mm
-
PE Stud wiring: cable 6 AWG (13mm
2
)
-
Tightening torque: 0.5Nm.
Pos. Name Function
J6.4
U1
Phase "L1", three-phase voltage input 230/460Vac
±
10%
J6.5 V1
Phase "L2", ", three-phase voltage input 230/460Vac
±
10%
J6.6 W1
Phase "L3", ", three-phase voltage input 230/460Vac
±
10%
PE
PE
Protective Earth Stud on Chassis
Table 3. -4 J6 AC Mains Power connector, A & B Size