3.3 Dissipation
To calculate cabinet cooling requirements, Table 3.
-
2 provides approximate equipment power dissipation values.
If the application employs regeneration, be sure to add the regen resistor power dissipation to the numbers
quoted in Table 3.
-
2, (use the continuous wattage rating of the regen resistor if the actual application regen
dissipation is unknown).
Power Dissipation (@ nom. current)
DS2110 3Amp 6Amp 8Amp 10Amp 14Amp 20Amp 25Amp 30Amp 50Amp 60Amp 100Amp
(Watts)
60 90
110 120 180 250 300 400 650 800 1200
Table 3. - 2 Estimated Power Dissipation for the DS2110 Servo-drives