CHAPTER 4.0 Getting Started
4-11
CDS7324 (FORMERLY LSF-0819)
Rev. A
INSTALLATION & USER’S MANUAL
4.11 High Power Application
Apply the appropriate 3-phase voltage
(230Vac/400Vac)
to the DS2110 controller and allow approximately
1.3
seconds for the softstart sequence to complete
.
If the drive has been set up correctly and all errors removed, the
softstart relay should close to indicate a successful soft start-up.
The “
Continuous Bus Voltage
” window provides an indication of the “
Detected DC Bus Voltage
”, ”Over
Voltage
Limit
” and “
Under Voltage Limit
”
“
DS2110
→
Drive Setup
→
DC Bus Monitoring
→
Continuous Voltage”
Figure 4.10 DC Bus Voltages