14 - 45
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.7 Leakage current breaker
(1) Selection method
High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits.
Leakage currents containing harmonic contents are larger than those of the motor which is run with a
commercial power supply.
Select a leakage current breaker according to the following formula, and ground the servo amplifier,
servo motor, etc. securely.
Make the input and output cables as short as possible, and also make the grounding cable as long as
possible (about 30cm (11.8 in)) to minimize leakage currents.
Rated sensitivity current 10 {Ig1 Ign Iga K (Ig2 Igm)} [mA] ..........(14.1)
K: Constant considering the harmonic contents
Leakage current breaker
Type Mitsubishi
products
K
Models provided with
harmonic and surge
reduction techniques
NV-SP
NV-SW
NV-CP
NV-CW
NV-HW
1
M
Servo
amplifier
Noise
filter
NV
Ig1 Ign
Iga
Ig2
Igm
Cable
Cable
General models
BV-C1
NFB
NV-L
3
Ig1:
Leakage current on the electric channel from the leakage current breaker to the input terminals
of the servo amplifier (Found from Fig. 14.1.)
Ig2:
Leakage current on the electric channel from the output terminals of the servo amplifier to the
servo motor (Found from Fig. 14.1.)
Ign:
Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF)
Iga:
Leakage current of the servo amplifier (Found from Table 14.5.)
Igm: Leakage current of the servo motor (Found from Table 14.4.)
Table 14.4 Servo motor's
leakage current
example (Igm)
Table 14.5 Servo amplifier's
leakage current
example (Iga)
Servo motor
output [kW]
Leakage
current [mA]
Servo amplifier
capacity [kW]
Leakage
current [mA]
0.05 to 0.5
0.1
0.1 to 0.6
0.1
0.6 to 1.0
0.1
0.7 to 3.5
0.15
1.2 to 2.2
0.2
5 7 2
3 to 3.5
0.3
5 0.5
7 0.7
Table 14.6 Leakage circuit breaker selection example
Servo amplifier
Rated sensitivity
current of leakage
circuit breaker [mA]
MR-J2S-10CP to MR-J2S-350CP
MR-J2S-10CP1 to MR-J2S-40CP1
15
MR-J2S-500CP 30
120
100
80
60
40
20
0
2 3.5
5.5
8 1422 38 80 150
30 60 100
Fig. 14.1 Leakage current example
(Ig1, Ig2) for CV cable run
in metal conduit
Cable size[mm
2
]
[mA]
Le
a
ka
ge
c
ur
re
nt
MR-J2S-700CP 50
Summary of Contents for MR-J2S-10CP
Page 11: ...A 10 MEMO ...
Page 19: ...8 MEMO ...
Page 45: ...1 26 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 181: ...6 20 6 MR Configurator SERVO CONFIGURATION SOFTWARE MEMO ...
Page 207: ...7 26 7 DISPLAY AND OPERATION MEMO ...
Page 219: ...8 12 8 GENERAL GAIN ADJUSTMENT MEMO ...
Page 229: ...9 10 9 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 231: ...10 2 10 INSPECTION MEMO ...
Page 249: ...12 8 12 OUTLINE DIMENSION DRAWINGS MEMO ...
Page 257: ...13 8 13 CHARACTERISTICS MEMO ...