670
Parameter
932
Manual pulse generator
input mode error
■
Description
The set range of the detailed parameter 1 "Manual
pulse generator input selection" is outside the
setting range.
■
Operation status at error occurrence
The LD75 READY signal (X0) does not turns ON.
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 33
■
Setting range
0, 1, 2, 3
935
Speed-position function
selection error
■
Description
The detailed parameter 1 "speed-position function
selection" is preset to 2 and the following three
conditions are not satisfied:
• Unit is "degree".
• Software stroke limits are invalid.
• Update current feed value.
■
Operation status at error occurrence
The LD75 READY signal (X0) does not turns ON.
■
Action
For speed-position switching control (ABS mode),
configure settings so that the three conditions on
the left are satisfied. When speed-position
switching control (ABS mode) is not to be
exercised, set 0 to speed-position function
selection and turn the PLC READY signal (Y0)
from OFF to ON.
■
Buffer memory address
Axis 1: 34
Axis 2: 184
Axis 3: 334
Axis 4: 484
■
Setting range
0, 2
950
Acceleration time 1
setting error
■
Description
The set value of the detailed parameter 2
"Acceleration time 1" is outside the setting range.
■
Operation status at error occurrence
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 36, 37
Axis 2: 186, 187
Axis 3: 336, 337
Axis 4: 486, 487
■
Setting range
1 to 8388608
951
Acceleration time 2
setting error
■
Description
The set value of the detailed parameter 2
"Acceleration time 2" is outside the setting range.
■
Operation status at error occurrence
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 38, 39
Axis 2: 188, 189
Axis 3: 338, 339
Axis 4: 488, 489
■
Setting range
1 to 8388608
952
Acceleration time 3
setting error
■
Description
The set value of the detailed parameter 2
"Acceleration time 3" is outside the setting range.
■
Operation status at error occurrence
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 40, 41
Axis 2: 190, 191
Axis 3: 340, 341
Axis 4: 490, 491
■
Setting range
1 to 8388608
Classification
of errors
Error
code
Error name
Operation status at error occurrence
Action/Related buffer memory address/Set
range (Setting with program)
Summary of Contents for MELSEC-L LD75D
Page 2: ......
Page 11: ...9 Memo ...
Page 176: ...174 ...
Page 264: ...262 ...
Page 266: ...264 ...
Page 267: ...265 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Page 268: ...266 ...
Page 269: ...267 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Page 270: ...268 ...
Page 271: ...269 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Page 272: ...270 Z ABRST1 instruction execution ...
Page 273: ...271 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Page 278: ...276 ...
Page 279: ...277 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Page 280: ...278 ...
Page 281: ...279 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Page 282: ...280 ...
Page 283: ...281 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Page 284: ...282 ...
Page 285: ...283 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Page 286: ...284 ...
Page 287: ...285 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Page 316: ...314 Memo ...
Page 685: ...683 APPENDICES A Appendix 1 Function Update Appendix 1 1 Function comparison Memo ...
Page 738: ...736 Memo ...
Page 817: ......