Code no. 22
Message:
You have CONNECTED some additional Power Units. Please do not forget to CONNECT the
corresponding Power Cables at the HS DC CBR.
Cause:
A DC Current Generator has been connected to the system.
Action:
Ensure that any connected DC Current Generator is also connected to the High-speed DC
Circuit Breaker.
Code no. 23
Message:
The HS DC CBR is still closed. For safety reasons, this program will not be terminated. Please
open the HS DC CBR first before terminating this program.
Cause:
This message is displayed when the operator tries to exit the BALTO software and the High-
speed DC Circuit Breaker is still connected and in the closed position.
Action:
Open the High-speed DC Circuit Breaker or disconnect the cables from the High-speed DC
Circuit Breaker.
Code no. 24
(Reserved for internal use.)
Code no. 25
Message:
The maximum number of tests for one report have been reached: Please insert a report name.
Cause:
The saved measurements table has reached the maximum number of lines.
Action:
In the ‘Report’ dialog, press ‘Save’ to save the currently saved measurements to a report file.
Then, clear the list to begin a new report.
Code no. 26
Message:
Value of I_ref too high or value of k2 (%) too high. Please reduce either I_ref or k2. Max I_ref
Value = …
Cause:
The injection specified by I_ref and k2 exceeds the maximum Current Injection capacity
Action:
Reduce the I_ref value, or
Reduce the k2 value.
Code no. 27
Message:
I-ref Value too high. Max value: …
Action:
Reduce the I-ref value.
Code no. 28
Message:
Slope speed too slow, please increase the speed to at least … A/s or reduce the current
Action:
Increase the ‘Slope’ value or decrease the ‘Delta I’ value.
Code no. 29
Message:
The value for di/dt should be > 0 ms. Please insert a higher value.
Action:
Increase the ‘Delta I’ value until the displayed ‘dt’ is greater than 0 ms.
Code no. 30
Message:
I-ref Value too high. Max value: …
Action:
Reduce the I-ref value.
Code no. 31
Message:
Value of measuring current too small. The current must be at least 100 A per Power Unit.
Action:
Increase the I-ref value to at least 100 A per connected DC Current Generator.
Code no. 32
Message:
I-ref Value too high. Max value: …
Action:
Reduce the I-ref value.
Code no. 33
Message:
The maximum number of tests for one report has been reached: Please insert a report name to
close this form.
Cause:
See code no. 25.
Action:
See code no. 25.