Attempting to start the Auto-Verification without a connected DC Current Generator, or with more than one
connected, will display an error message with code no. 49.
Press ‘START’ to begin the Auto-Verification process. The system will inject various levels of current and display the
measured current and measured current difference.
The results are displayed in the table as follows:
Current differences that exceed 5% of Iout are shown in red, indicating a problem with the DC Current Generator or
system calibration:
Pressing ‘RESET’ will clear the results table for performing another test.
www.megger.com
91
Operation