Fault message.
Please, check the connections and the polarity.
Calibration result.
Example:
The value of the shunt is 6.000 A / 90 mv and the max value of the expected current is not higher than 7.500 A.
Inom = 7.500 A
As feedback - trip contact - an auxiliary contact from the DC Protective Relay is utilized, select between:
NC - Normal Closed, or
NO - Normal Open.
The connection to the voltage output is automatically done.
Adjust output range
1
2
5
3
4
1
2
5
3
4
Fig 47:
Adjust output range.
www.megger.com
+ 7.500 A
112
Secondary Injection.