5. Disconnect the cables from the power supply to the system board and all internal components. Be sure
to make a note of the cable routing.
Attention:
Support the power supply while you remove the mounting screws. After the screws are
removed, the power supply is loose and can damage other components in the server.
6. While you support the power-supply, remove the three screws from the pivot bracket that secure the
power supply to the chassis; then, lift the power supply off the chassis. Save the screws to use when you
install the replacement power supply.
0000
0000
0000
0000
0000
0000
00
00
00
00
1
Power supply retaining screws
2
Power supply assembly
7. If you are instructed to return the power supply, follow all packaging instructions, and use any packaging
materials for shipping that are supplied to you.
Installing a power supply
To install a power supply, complete the following steps.
Note:
Approximately 1 to 3 minutes after the server is connected to ac power, the power-control button
becomes active.
1. Align the screw holes in the power supply cage pivot bracket with the corresponding screw holes on
the rear of the chassis.
Chapter 7
.
Installing and replacing FRUs
185
Summary of Contents for ThinkServer TD200
Page 2: ......
Page 8: ...viii ThinkServer TD200 Hardware Maintenance Manual ...
Page 28: ...20 ThinkServer TD200 Hardware Maintenance Manual ...
Page 138: ...130 ThinkServer TD200 Hardware Maintenance Manual ...
Page 264: ...256 ThinkServer TD200 Hardware Maintenance Manual ...
Page 300: ...292 ThinkServer TD200 Hardware Maintenance Manual ...
Page 327: ...Lenovo product service Appendix A Getting help and technical assistance 319 ...
Page 328: ...320 ThinkServer TD200 Hardware Maintenance Manual ...
Page 338: ...330 ThinkServer TD200 Hardware Maintenance Manual ...
Page 344: ...336 ThinkServer TD200 Hardware Maintenance Manual ...
Page 345: ......
Page 346: ...Part Number Printed in USA 1P P N ...