Section 5: Programming
[899] Template Programming
Template programming allows quick programming of the minimum functions required for basic operation. This section is
used to view current template programming options and to define certain system parameters. Press the (#) key to accept the
displayed value and advance to the next option. The following options are available:
l
5-digit Template Code: Displays the current 5-digit template programming code (default: 00000). Each digit in the
code selects a set of pre-defined programming options, as described below:
l
Digit 1 - zone 1-8 definition options
l
Digit 2 - system EOL options
l
Digit 3 - alarm controller communications options
l
Digit 4 - reporting code configurations
l
Digit 5 - DLS connection options
l
Central Station Telephone Number: The phone number used to contact the central monitoring station (32 character
limit).
l
Central Station Account Code: The account code used in programming section [310]. This is a 4 or 6-digit entry.
l
Partition Account Code: Used to identify partition-specific events. All 4 digits must be entered in order to complete the
entry.
l
This account code is entered into programming section [310][001].
l
DLS Access Code: The 6-digit DLS access code used in programming section [403].
l
Partition 1 Entry Delay: The 3-digit entry delay duration for partition 1, in seconds, used in programming [005][001]
option 1.
l
Partition 1 Exit Delay: The 3-digit exit delay duration for partition 1, in seconds, used in programming section [005]
[001] option 3.
l
Installer Code: The 4, 6 or 8-digit installer access code used in programming section [006][001].
For more information on template programming, see "Template programming tables" on page 258.
Systems Information
[900] System Information
[000] – Control Panel Version
This read-only section contains the model number, software version, hardware revision and serial number of the alarm con-
troller
.
For example, an entry of 1234 is read as version 12.34.
[001]-[524] – Module Information
This read-only section is used to view the model number, software version, and hardware revision information of the mod-
ules enrolled on the alarm system.
To view information for a specific module, scroll to the corresponding section:
[001]-[016] keypads
[101]-[130] 8-zone expansion module
[201]-[216] 8-output expansion module
[301] -[330] 8 zone expansion module
[460] Alternate Communicator
[461] HSM2Host module
[481] 2 Way Audio Module
[501]-[504] 1A power supply module
[521]-[524] high-current output modules 1-4
[551]-[554] 3A power supply
[601]-[608] Corbus repeater
[901] Installer Walk Test Mode Enable/Disable
This mode tests the operation of each detector in the system. Enter section [901] to initiate a walk test. While in Walk Test
mode, the Ready, Armed, and Trouble LED's on the keypad flash to indicate that the test is active. When a zone is tripped
during the test, a 2-second tone sounds on all system keypads to indicate that the zone is working correctly.