Section 2: Installation
Figure 2-33 LED output with current limiting resistor and optional relay driver output.
UL Compatibility ID For FSA-210B Series is: FS200
Note:
For ULC listed installations, use FSA-210A and FSA-410A series.
Bell wiring
These terminals supply 700 mA of current at 10.8 - 12.5 VDC for commercial/ residential installations. To comply with NFPA
72 Temporal Three Pattern requirements, section [013] Opt [8] must be ON. Note that steady, pulsed alarms are also sup-
ported. Temporal 4 cadence for CO alarm notification is also supported.
Figure 2-34 Bell wiring
The Bell output is supervised and power limited by 2 A hardware protection. If unused, connect a 1000
Ω
resistor across
Bell+ and Bell- to prevent the panel from displaying a trouble. See "Troubleshooting" on page 59.
Telephone line wiring
Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an RJ-31x connector as indicated in the following diagram.
For connection of multiple devices to the telephone line, wire in the sequence indicated. Use 26 AWG wire minimum for wir-
ing.
Figure 2-35 Telephone line wiring
Note:
Ensure that all plugs and jacks meet the dimension, tolerance and metallic plating requirements of 47 C.F.R. Part 68,
Sub-Part F. For proper operation, no other telephone equipment must be connected between the control panel and the tele-
phone company facilities.
- 39 -