Section 5: Programming
[001]-[008] Partition Account Codes
Use these sections to program account codes for each partition.
When using formats other than SIA, these account codes identify the alarm system to the central station when com-
municating partition-specific events.
Note:
The system will not communicate if the account code is not programmed. When this condition occurs, Account Code
Not Programmed is briefly displayed on the keypad when exiting Installer Programming mode.
Note:
If no phone numbers are programmed, the error message does not occur.
[311]-[318] Partition Call Directions
Use this programming option to select the central station receivers that partition events are communicated to. Call directions
can be programmed for each partition. Each event can be sent to one of four receivers.
[001] Alarm/ Restore
These options control which receiver paths are enabled for Partition 1-8 Alarm and Restore event reporting codes.
To assign an event to a receiver, select one of the following options:
[01] Receiver 1
[02] Receiver 2
[03] Receiver 3
[04] Receiver 4
[002] Tampers (Including System Tampers)/ Restore
These options control which receiver paths are enabled for Partition 1-8 Tamper and Restore event reporting codes.
To assign an event to a receiver, select one of the following options:
[01] Receiver 1
[02] Receiver 2
[03] Receiver 3
[04] Receiver 4
[003] Openings/ Closing
These options control which receiver paths are enabled for Partition 1-8 Opening and Closing event reporting codes. To
assign an event to a receiver, select one of the following options:
[01] Receiver 1
[02] Receiver 2
[03] Receiver 3
[04] Receiver 4
[350] Communicator Formats
Use this programming option to assign a communicator format to each of the four receivers programmed in section [301].
The available communicator formats are as follows:
03
DTMF Contact ID
04
SIA FSK
To assign a communications format, select a receiver (option [001]-[004]) then enter the 2-digit code corresponding to the
chosen format. For detailed descriptions of each format, see "Reporting codes" on page 250.
[377] Communication Variables
[001] – Swinger Shutdown
Alarms/Restores
This value defines the number of communication attempts made for alarm/restore events, per zone, before the zone goes
into swinger shutdown. Valid entries are 000 to 014. For CP-01, entries are from 001-006.
Once the programmed number of alarm/restore events have been communicated, no further alarm/restore events for the
zone are communicated until swinger shutdown is reset. The last restore event is not communicated until swinger is cleared.