Section 2: Installation
Figure 2-32 TEOL wiring
The following table shows zone status under certain conditions for TEOL:
Table 2-8 TEOL loop status
Loop resistance
Loop status
0 Ω (short)
Fault
Infinite Ω (open)
Tamper
5600 Ω
Restored
11200 Ω
Alarm
21200 Ω (alarm and fault/mask)
Mask
15600 Ω (fault/mask)
Fault
Note:
Resistor values are configurable in section [004].
PGM wiring
Min/max operating voltages for devices, sensors and modules is
9.8 V DC - 14 V DC.
PGMs switch to ground when activated from the alarm controller. Connect the positive side of the device to the AUX+ ter-
minal and the negative side to a PGM terminal.
PGM 1, and 4 supply up to 100 mA; PGM 2 and 3 supply up to 300 mA.
A relay is required for current levels that exceed the maximum limits.
PGM2 can also be used for two-wire smoke detectors or 24-hour burglary input alarm.
Note:
Use only SEOL resistors on Fire zones.
- 38 -