Section 5: Programming
OFF: The system can be armed even when troubles are present.
Note:
When Engineer’s Reset is on, trouble conditions cannot be overridden. Zone Expander supervisory troubles cannot
be acknowledged and overridden. These conditions must be restored before the panel can be armed.
Note:
When [024][3] is enabled, AC/DC Inhibit Arming, the AC or DC trouble must be restored before the system can be
armed.
[021] System Option 9
EN
1 – Trouble Display
ON: If the panel is both armed and keypad blanking is active, when a trouble is present the keypad trouble LED will remain
off . When the system is disarmed, or if blanking is removed, the trouble LED will be active if a trouble is present.
OFF: The trouble LED will turn off when keypad blanking is active in armed or disarmed state.
EN
2 – Keypad Blanking while Armed
ON: If [016][3] is disabled within 30 seconds after the exit delay terminates, the keypad blanks (no indicator lights).
OFF:The keypad blanks when the system is armed or disarmed.
Note:
For systems compliant with EN50131-1 and EN50131-3, option [021] bit 2 “Keypad blanking while armed” must be
ON.
3 – Reserved
4 – Ready Display
ON: The keypad ready LED will continue to show system ready status while keypad blanking is active.
OFF: The keypad ready LED will turn off when keypad blanking is active.
5 – PGM Blanking
This feature is meant to be used in conjunction with the keypad blanking while armed feature.
EN
ON:This feature is necessary to comply with EN50131-1:2006.
When the system enters blanking mode, any PGMs programmed as Armed Status, Ready Status, Away Armed Status, or
Stay Armed Status will de-activate. If blanking is cleared by pressing a key, or entering an access code depending on how
the panel is configured, these PGMs must re-activate if they would have normally been ON if blanking was disabled.
OFF: When the system enters blanking mode, any PGMs programmed as Armed Status, Ready Status, Away Armed Status,
Stay Armed Status) operate normally.
6 – Armed Display
ON: The keypad armed LED will continue to show Armed status while keypad blanking is active.
OFF: The keypad armed LED will turn off when keypad blanking is active.
7 – Open Zones Cancels Arming
ON: The system cannot be armed while zones are open unless the zones are bypassed using [*][1]. In order to bypass open
zones, the bypass attribute needs to be enabled for the zone.
OFF: Open zones do not prevent arming.
8 – Audible Exit Delay for Stay Arming
ON: When the system is armed in Stay mode the exit delay is sounded by 1 beep every 3 seconds.
OFF: When the system is armed in Stay mode the exit delay is silent.
[022] System Option 10
1 – [F] Key Option
ON: When the [F] key is pressed, acknowledge beeps are only emitted from the keypad. The siren does not sound fire alarm.
OFF: [F] key acknowledgment beeps are emitted from the keypad and sounds for fire alarm.
2 – Reserved
3 – Reserved
EN
4 – Transmission Counter in Hours
ON: The alarm system sends a test transmission after the programmed number of hours in the test transmission cycle (Sec-
tion [377], Option 003).
OFF: The alarm system sends a test transmission after the programmed number of days.