Appendix 5: Regulatory approvals
- B - use of one self-powered warning device and one ATS SP3 required (internal dialer or ethernet or plug-in cellular mod-
ule)
- C - use of dual path ATS DP2 required (any combination of internal dialer and ethernet and/or cellular module)
- D - use of an ATS SP4 required (internal ethernet or plug-in cellular module with encryption enabled)
- E - use of dual path ATS DP3 required (combination of internal ethernet and plug-in cellular module with encryption
enabled)
For EN50131 compliant installations, with alarm control panels HS3248, HS3128 and HS3032, only the intrusion portion of
the alarm system may be activated.
For EN50131 compliant installations, the following functions must be disabled:
- Fire Alarm
- CO Alarm
- Auxiliary (Medical) Alarm functions
- In Section 861-21, options 1 and 2 must be off.
For EN50131 compliant installations, the following zone types must not be used:
007 – Delayed 24-Hour Fire
041 -– 24-Hour CO
049 – 24-Hour Flood
008 – Standard 24-Hour Fire
045 – 24-Hour Heat
052 – 24-Hour Non-Alarm
025 – Auto Verified Fire
046 – 24-Hour Medical
056 – 24-Hour High Temperature
027 – Fire Supervisory
047 – 24-Hour Emergency
057 – 24 Hour Low Temperature
040 – 24-Hour Gas
048 – 24-Hour Sprinkler*
071 – Door Bell
In this configuration, no non-mandatory events are generated in the Event Buffer and compliance with minimum 500 man-
datory events storage (Grade 3) is ensured as per Section 8.10.1 in EN50131-3. Compliance labeling should be removed or
adjusted if non-compliant configurations are selected.