Appendix 5: Regulatory approvals
The product is labeled with the UL and ULC listing marks along with the SIA CP-01 compliance statement (Also Classified in accordance with SIA-CP-01 Standard) as
proof of compliance with the above mentioned standards. For further information on this product’s listings please also refer to the official listing guides published at the
UL web site (www.ul.com) under Online Directions Section.
UL/ULC Residential Fire and Burglary Installations:
For ULC Installations, refer to the Standard for the Installation of Residential Fire Warning Systems, CAN/ULC-S540.
l
Control Unit must be enclosed in model HSC3010C or HSC3020C enclosure.
l
Power supply model SOY-1800360NA (HS65WPSNA) must be employed.
l
24 h standby power must be provided for fire applications and 4h for burglary only applications (AC trouble must be transmitted to SRC).
l
One DSC Model RM-1 or RM2 end-of-line supervision relay module must be used.
l
Priority of signals needs to be set Fire, CO/ Medical, Burg, Panic, AUX (Flood).
l
All burglary-type zones shall be configured with SEOL or DEOL configuration. Use model EOLR-2
l
(refer to section [002], bit 10 or 11 shall be ON)
l
Use at least one PG9926/ PG9916/ PG9936 Smoke Detector for Fire Installations (section [001], fire zone shall be programmed as type 025)
l
The entry delay shall not exceed 45 seconds (see section [005])
l
The exit delay shall not exceed 60 seconds (refer to section [005])
l
The minimum Bell Time-out is 4 minutes (refer to section [005])
Note:
Connect Bell output to a UL/ULC Listed audible device (e.g., UL File S8534, model TS-443S-6), rated to operate over the range of 10.8 to 12.5 VDC and 85dBA
minimum. Wireless sirens PG9901 and PG9911 may also be used as audible devices.
Note:
For ULC Residential Fire installations, minimum bell time-out is 5 min. For UL Home Health Care installations, minimum bell time-out is 5 min. For UL Com-
mercial Burglary installations, minimum bell time-out is 15 min.
l
Temporal Three Fire Signal shall be enabled (section [013], opt.8 ON)
l
Arm/Disarm Bell Squawk shall be enabled when using wireless key PG4939/PG4929/PG4949 (section [014], option 1 shall be ON)
l
A code shall be required for bypassing (section [023], option 4 shall be ON)
l
Trouble beeps shall be enabled (section [022], option 7 shall be ON)
l
AC trouble indication LED shall be enabled (Keypad Programming, section [022], options 5 and 6 shall be ON)
l
DACT Communicator shall be enabled for Supervising Station Monitoring (section [380], option 1 shall be ON)
Note:
The DACT communicator for this product has no line security.
Telephone Line Monitoring (TLM) shall be enabled (section [015], option 7 shall be ON)
This product is programmed to perform 5 attempts for communication of an event to the supervising station. If unsuccessful, a Fail To Communicate (FTC) trouble is
generated.
Test transmission cycle shall be set (refer to section [351]) for monthly transmission for UL residential burglary applications and to 7 days for UL residential fire applic-
ations.
Note:
For ULC Residential/Commercial installations set for daily test transmission.
l
For UL Residential Fire installations, [*][2] requires code shall be enabled (Section [023] option 5 ON) and latching troubles shall be enabled (Section [019] option
2 ON)
l
If a repeater is needed, two repeaters model PG9920 shall be used to ensure proper signal routing.
l
Wireless Supervision window shall be set to 4 hours for Fire Installations (Wireless Programming, section [804]>[802] shall be programmed with the value 16).
l
Wireless Supervision window shall be set to 24 hours for Burglary Installations only (Wireless Programming, section [804]>[802] shall be programmed with the
value 96).
l
RF Jam detection shall be enabled (refer to Wireless Programming (section [804][801], option 00 shall be OFF).
l
New Alarms will Disconnect 2-way Audio (section [022], option 6 OFF).
Requirements for UL985 6th edition compliant installations:
For UL residential fire applications (including CO) compliant with UL985 6th edition, the following guidelines shall be respected:
l
Two UL listed compatible keypads (for example HS2LCDPRO, HS2TCHPRO(BLK), HS2LCDRFPRO9) shall be used, each having communication bus wir-
ing directly connected to the RED/BLK/YEL/GRN terminals located on the main control panel board assembly.
l
Power loop supervision relay model RM-1(C) or RM-2 shall be connected to AUX power output to report wiring faults if it is used for powering fire/CO detec-
tion devices.
l
Section [023] option 5 shall be
ON
. A user code shall be required to view the [*] [2] trouble menu. When enabled, trouble beeps will only be silenced when the
[*] [2] has been entered and exited.
l
In section [377] [003] a test transmission must be sent to the monitoring station every 7 days (default: 007).
l
In section [377] [004], the default time is programmed for 4.45 a.m (0445). The panel will generate a random test transmission time within a ± 60 minute win-
dow.
l
If a repeater is required, two of the PG9920 models shall be used for proper signal routing.
l
Latching troubles shall be enabled (section [019] option 2 must be set to
ON
).
l
In a combination fire and burglary application, fire alarm detection devices shall not be powered from the same AUX output (control panel, zone expander,
power supply) as burglary alarm initiating devices.
l
Power supply wiring for fire alarm detection devices (smoke detectors, CO Detectors) shall be connected to the control panel AUX output (located
on the main control panel board assembly).
l
Power supply wiring for burglary alarm initiating devices (motion detectors, magnetic contacts, glass break detectors, etc.) shall be connected to
the compatible power supply modules AUX outputs (located on the power supply module board assembly, for example HSM3350, HSM3204CX) or
expander module AUX output (located on the expander module board assembly, for example HSM3408).
ULC Commercial Burglary Security Levels I-IV:
The following wireless PowerG devices models are ULC listed under ULC-S304 requirements for use in Commercial Burg applications rated for security level 1.
l
PG9914
l
PG9905
l
PG9920
l
PG9975
l
PG9922
l
PG9924
l
PG9929
l
PG9934P
l
PG9935
l
PG9938
l
PG9939
l
PG9944
l
PG9945
l
PG9949
l
PG9974
l
PG9974P
l
PG9984
l
PG9984P
l
PG9985
l
PG9994
- 267 -