Section 7: Troubleshooting
Trouble [4] AC Failure
Press [04] to determine specific trouble
Trouble
Troubleshooting
[01] Zone 1-248 AC
[03] Siren 1-16 AC
[04] Repeater 1-8 AC
[05] HSM2300 1-4 AC
[06] HSM2204 1-4 AC
[07] Alarm Controller
[08] HSM3204CX AC
[09] HSM3350 AC
An AC trouble has been detected on a device or module.
Verify voltage measured across DC input terminals is 16-20VDC. Replace HSM65W
power adapter if required.
For the HSM2204 or HSM2300 modules, ensure a 40VA 16.5VAC transformer is
being used. Terminal voltage should be 16-17VAC. Replace transformer if required.