Appendix 5: Regulatory approvals
The wireless supervision window shall be set to 4h for such applications and the tamper detection for removal from mounting location shall be enabled.
UL Central Station and Police Connect with Standard or Encrypted Line Security Service
l
The installation must use the integral Ethernet communicator or the plug-in cellular modules Models LE9080, 3G9080 or 3H9080, which communicates over Cel-
lular Data Network or an Ethernet network 10/100BaseT to the compatible Sur-Gard System I/II/III/IV/5 receiver.
l
Polling time shall be 200 seconds and compromise detection time shall be 6 minutes.
l
For Encrypted line security applications, the integral Ethernet communicator or the plug-in cellular modules Models LE9080, 3G9080 or 3H9080 shall have the
Encryption Key enabled (AES128 bit encryption algorithm is validated under NIST Certificate No.5371 and 5372.)
l
Wireless Supervision window shall be enabled (refer to Wireless Programming, sections [804]>[802].)
l
Open/Closing acknowledgment shall be enabled (Not required for Police Station connected systems.)
l
Bell test for police station connect.
UL Local, Central Station and Police Connect with No Line Security Service
l
All zones shall be programmed as end-of-line supervised.
l
All intrusion zones shall be programmed as audible.
l
The installation shall use a Bell UL Listed for Mercantile local alarms (e.g., Honeywell Model AB-12M bell housing). Connections from the control unit to the bell
shall be made in conduit. (Optional for central Station).
l
The Bell shall be tested daily. Alternate option is to have bell squawk enabled for arming/disarming. The Bell activation cannot be delayed for more than 5 mins.
l
The bell timeout shall be programmed for 15 minutes minimum.
l
At least one system remote keypad with tamper switch shall be employed
l
The integral communciator (DACT/IP) or plug-in cellular module shall be enabled and shall be programmed to provide a low battery transmission.
l
The control panel shall be in a separately listed HSC3030CAR attack resistant enclosure.
l
The maximum entry delay time shall not exceed 45s (25s for a local) as a result of the attack test. The maximum exit delay time shall not exceed 60 s.
l
A tamper switch shall be used to protect the enclosure cover of the control unit. A tamper switch shall also be used on the keypad rear to detect removal from the
wall.
l
24 h check in transmission shall be enabled.
l
Open/Closing acknowledgement enabled.(Not Police Station).
l
The Installation shall use the internal communicator (DACT or IP) alone or in conjunction with plug-in cellular modules Models LE9080, 3G9080 or 3H9080, which
communicate over Cellular Data Network or an Ethernet network 10/100BaseT to the compatible Sur-Gard System I/II/III/IV/5 receiver.
UL Home Health Care Signaling Equipment
l
There must be at least two keypads, one of the compatible keyapds models HS2LCDPRO, HS2LCDRFPRO9, HS2LCDWFPRO9, HS2LCDWFVPRO9,
HS2TCHPRO(BLK).
l
Each system shall be programmed to activate an audible Trouble signal within 90 seconds upon loss of microprocessor memory
ULC Central Station Fire and Burglary Monitoring Installations
l
For installation requirements, levels of security, communication modules and configurations (Refer to the ULC Installation Guide for PowerSeries Pro, P/N
#29010346).
l
HS2TCHPRO(BLK) touch screen keypad is for supplementary use only with ULC Commercial Fire Monitoring.
l
For Commercial Fire monitoring, the primary power failure transmission may be delayed up to 3h and Bell shall be disabled.
Note:
As per ULC Bulletin 2017-02A, ULC Fire and Security Systems Group is accepting the use of MFVN digital telephone services for connection of digital dialer
transmitters ULC listed to be connected to the public switched telephone network communication system. Since the MFVN communication channel technologies
available are not provided with 24 hour standby power on the equipment and facilities used between the premises and the signal receiving center, it is required that, for
passive communication channels used in monitored protective signaling system installations, the testing time of the passive communication channels should be
reduced from the current 24 hours to 6 hours to better ensure that the system and communication channels are operating in their intended manner to reduce the life
safety risk. A change in testing frequency for intrusion alarm systems is not required due to the many different levels of line security options available for these system
types, which should be applied based on communication supervision needs for each installation.
For PowerSeries Pro panels, the following programming options shall be adjusted to meet the new 6 hour test transmission when used in ULC-S561 compliant install-
ations:
l
Section [022] turn option 4 ON for hours.
l
Section [377] option [003] set to 006 (for 6 hours).
l
Section [309] option [002] enable test transmission for all applicable receivers.
Programming
The notes in the programming sections of thePowerSeries Pro Reference Manual describing the system configurations for UL/ULC listed installations shall be imple-
mented.
Control of the Protected Premises
In order to have a UL certificated system, the protected area shall be under the responsibility of one ownership and management (i.e., one business under one name).
This may be a group of buildings attached or unattached with different addresses but under the responsibility of someone having mutual interest. The person of mutual
interest is not the alarm-installing company.
Note:
This does not apply to strip mall applications where each independent business must have their own separate alarm system.
e.g.,1: A commercial partitioned system that has an office and a warehouse area in a building where each area can be armed or disarmed independently. e.g.,2: A res-
idential system partitioned so that the garage area is armed separately from the house.
Each of the above examples is under the sole responsibility of a single owner. The bell and DACT power supply must be in a protected area including partitioned sys-
tems. The bell and DACT power supply must be located where it can be heard by the person or persons responsible for maintaining the security system during the
daily arming cycle.
Bell Location
The alarm sounding device (bell) shall be located where it can be heard by the person operating the security system during the daily arming and disarming cycle.
Protection of the Control Unit