Appendix 6: Wiring diagrams
6.8 PGM wiring
PGMs switch to ground when activated by the control panel.
Connect the positive side of the device to the AUX+ terminal and the negative side to a PGM terminal.
The Minimum/maximum operating voltages for devices, sensors and modules is 9.8 Vdc - 14 Vdc.
Current output is as follows:
PGM1, PGM4: 100mA
PGM2, PGM3: 300mA
For currents levels greater than 300mA, a UL listed RM-1 or RM-2 relay module is required.
PGM2 can also be used for 2-wire smoke detectors.
PGM 1, LED output with current limiting resistor and optional relay driver output.
Note:
Use only SEOL resistors on FIRE ZONES.
2-wire smoke detectors initiating circuit
l
Style B (Class B), Supervised, Power Limited
l
Compatibility Identifier HS3-1
l
DC Output Voltage 9.4-13.8 VDC
l
Detector Load 2 mA (MAX)
l
Single-end-of-line (SEOL) Resistor 2200Ω
l
Loop Resistance 24Ω (MAX)
l
Standby Impedance 1250Ω (NOM)
l
Alarm Impedance 664Ω (MAX)
l
Alarm Current 97 mA (MAX)
l
Maximum number of 2-wire Smoke Detectors 18
2-wire smoke detectors
4-wire smoke detectors
Compatibility ID For FSA-210 Series is: FS200
RM-1/RM-2 POWER LOOP
SUPERVISORY RELAY
Compatible DSC 2-wire smoke detectors:
FSA-210A Series for ULC
FSA-210B Series for UL
FSA-210C Series for EU
Compatible DSC 4-wire smoke detectors:
FSA-410A Series for ULC
FSA-410B Series for UL
FSA-410C Series for EU
- 281 -