Section 2: Installation
Wireless transceiver module
The HSM2HOSTx 2-way wireless module provides communication between wireless devices and the alarm controller.
Note:
The HSM2HOST must be used with the HSC3020CP plastic enclosure, or in its own separate enclosure.
Connect the HSM2HOSTx to the 4-wire Corbus of the alarm controller according to the following diagram.
Figure 2-24 HSM2HOSTx wiring diagram
After you have completed the wiring, reconnect power to the security system. Board current draw: 35 mA
Power supply wiring
HSM2300/2204
The HSM2300/2204 power supply/high-current output module provides up to 1 A of additional current and can be used to
add up to four programmable outputs (HSM2204 only) to the alarm system.
The 4-wire Corbus connection provides communication between the module and alarm panel. Connect the RED, BLK, YEL
and GRN terminals to the Corbus terminals on the alarm controller. If O1 is not used, connect to Aux+ with a 1 K resistor.
Board current draw: 35 mA.
Figure 2-25 HSM2300/2204 power supply wiring
AUX**
TO
EXPANSION
MODULE
KEYBUS
CONNECTION
TO CONTROL
PANEL
RED
BLK
YEL
GRN
RED*
BLK*
YEL
GRN
Battery standby capacity is at least for 24 hours for
Fire Applications.
Recommended Battery: DSC model BD7-12.
*
Red, Blk, 12 V
DC
@ 20mA
**
Refer to the Specifications Chart above for
the maximum current draw.
BATTERY
12V 7Ah
Maximum battery
charge current is
360 mA
BATTERY 1
12V 7Ah
Maximum battery
charge current is
360 mA
Residential
Burglary
UL/ULC residential
fire applications
TRANSFORMER
16.5V
AC
/ 40VA
PTD1640U /
PTD1640
TO
BLK
BATTERY 2
12V 7Ah
Same rating as
Battery 1
CON1
BAT+ BAT-
120VAC/
60Hz
Primary
EU, South Africa,
Australia, NZ etc:
primary 230VAC/ 50/60Hz
- 32 -