Appendix 7: Specifications
Appendix 7: Specifications
Zone Configuration
l
32, 128 or 248 wireless zones supported and up to 8 hardwired zones available on the controller
l
41 zone types and 15 programmable zone attributes
l
Zone configurations available: normally closed, single EOL resistor, DEOL resistor, and TEOL resistor.
l
Hardwired zone expansion (fully supervised) available using the model HSM2108 or HSM3408 (eight zone
expander module)
l
Wireless zone expansion (fully supervised) available using the HSM2Host 2-way wireless integration module oper-
ating at 915 MHz (North America), 433 MHz (Europe) and 912-919 MHz (international)
Access Codes
l
Up to 1003 access codes: 1000 (level 2-EN), one installer code (level 3-EN), one maintenance code, and one guard
code.
l
Programmable attributes for each user code
l
Access codes are either 4, 6 or 8 digits in length, depending on the setting of programming section [041]. Duplicate
codes are not valid.
Note:
For EN50131-1 Grade 2 compliant systems using 100 access codes or less, 6 digit codes must be used. If using more
than 100 access codes, 8 digit codes must be used. For EN50131-1 Grade 3 compliant systems 8 digit codes must be used.
Warning Device Output
l
2 remote, wireless indoor/outdoor warning devices supported: models PGX901 (indoor), PGX911 (outdoor) (X=4, 8,
or 9)
l
Programmable as steady, pulsed or temporal three (as per ISO8201) and temporal four (CO alarm) output
l
Warning device sounds alarms in the following priority: fire, CO, burg
Note:
For NFA2P certified systems the delay for operating the warning device shall be set to max. 10 min.
Memory
l
CMOS EEPROM memory
l
Retains programming and system status on AC or battery failure for 20 years min. (not verified by UL)
Power Supply - North America
l
Power Supply:HS65WPSNA (cord connected) and HS65WPSNAS (hardwired, use in ULC Commercial Burg Secur-
ity Level IV and ULC Commercial Fire Monitoring applications)
l
Primary: 120 VAC, 60 Hz, Energy Efficiency Class VI
l
Secondary: 18 V DC, 3.6 A Limited Power Source (LPS)
l
Model HS65WPSNA mounted in the same enclosure or outside, cord connected
l
Model HS65WPS mounted in the same enclosure, permanently connected
Power Supply - International
l
Power Supply: HS65WPS
l
Primary: 100-240 V AC, 50 Hz, 1.7 A, Energy Efficiency Class VI
l
Secondary: 18 Vdc, 3.6A, LPS
l
Mounted in the same enclosure, permanently connected
Note:
For installations using the power supply module mounted inside the cabinet, replace fuse only with the same type (20
mm) rated New fuse rating 250 V/3.15 A Slow Blow.
Regulated power supply:
l
3.6 A regulated, supervised
l
Type A as per EN50131-6 Standard
l
FET protected for Bell, Aux+ and Battery terminals
l
Reverse battery detection/protection
l
Supervision for input power and low battery
l
Normal and high current battery charge options
l
Supervised battery charging circuit
Current draw (control panel board assembly):
l
120 mA (nominal)
Bell Output:
- 283 -