DP module 12: Extended command channel
Module 12, extended command 54dec (36hex):
read current parameters of the connected AS-i slaves
9-60
Response from controllere (gateway)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0 B=0
M
0/1
reflected user ID
reflected command number = 36
hex
2
reserved = 0
reserved = FF
hex
3
Param. Slave 4(A)
Param. Slave 3(A)
Param. Slave 2(A)
Param. Slave 1(A)
4
Param. Slave 8(A)
Param. Slave 7(A)
Param. Slave 6(A)
Param. Slave 5(A)
5
Param. Slave 12(A)
Param. Slave 11(A)
Param. Slave 10(A)
Param. Slave 9(A)
6
Param. Slave 16(A)
Param. Slave 15(A)
Param. Slave 14(A)
Param. Slave 13(A)
7
Param. Slave 20(A)
Param. Slave 19(A)
Param. Slave 18(A)
Param. Slave 19(A)
8
Param. Slave 24(A)
Param. Slave 23(A)
Param. Slave 22(A)
Param. Slave 21(A)
9
Param. Slave 28(A)
Param. Slave 27(A)
Param. Slave 26(A)
Param. Slave 25(A)
10
Param. Slave 1B
Param. Slave 31(A)
Param. Slave 30(A)
Param. Slave 29(A)
11
Param. Slave 5B
Param. Slave 4B
Param. Slave 3B
Param. Slave 2B
12
Param. Slave 9B
Param. Slave 8B
Param. Slave 7B
Param. Slave 6B
13
Param. Slave 13B
Param. Slave 12B
Param. Slave 11B
Param. Slave 10B
14
Param. Slave 17B
Param. Slave 16B
Param. Slave 15B
Param. Slave 14B
15
Param. Slave 21B
Param. Slave 20B
Param. Slave 19B
Param. Slave 18B
16
Param. Slave 25B
Param. Slave 24B
Param. Slave 23B
Param. Slave 22B
17
Param. Slave 29B
Param. Slave 28B
Param. Slave 27B
Param. Slave 26B
18
not used
not used
Param. Slave 31B
Param. Slave 30B
Example:
Word no.
Value [hex]
Description
1 0636
M=0: AS-i master 1
06 = reflected user ID changes e.g. to 6
36 = reflected command number 54
2 00FF
reserved
3 4321
current parameters of slave 1(A) to slave 4(A):
1 = slave 1(A), 2 = slave 2(A), 3 = slave 3(A), 4 = slave 4(A)
4 8765
current parameters of slave 5(A) to slave 8(A):
5 = slave 5(A), 6 = slave 6(A), 7 = slave 7(A), 8 = slave 8(A)
… …
…
9 6543
current parameters of slave 29(A) to slave 1B:
3 = slave 29(A), 4 = slave 30(A), 5 = slave 31(A), 6 = slave 1B
… …
…
17 FE98
current parameters of slave 26(B) to slave 29B:
8 = slave 26B, 9 = slave 27B, E = slave 28B, F = slave 29B
18 0098
current parameters of slave 30B to slave 31B:
8 = slave 30B, 9 = slave 31B
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...