DP module 7: Command channel
Module 7, command 14dec (0Ehex):
read configuration error counter
8-15
8.14
Module 7, command 14
dec
(0E
hex
):
read configuration error counter
Structure
Request of DP master
Bit
MM = master no. (1…2)
Byte
7
6
5
4
3
2
1
0
1
0 0
0E
hex
2
MM 0
3
0
not used *)
4
0
not used *)
Response from controllere
Bit
Byte
7
6
5
4
3
2
1
0
1
D7 D6
0E
hex
2
copy of the request
D6 = command code
D7 = error code
→
page
, table at the bottom
3
error counter high byte
4
error counter low byte
provides the number of configuration errors of the master
since power on or reset
Example: read configuration error counter on AS-i master 2
Request of DP master
Byte no.
Value [hex]
Description
1
0E
0E = command 14
2 80
(master no.
2 * 64
)
= 128
dec
=
80
hex
3
00
not used *)
4
00
not used *)
Response from controllere
Byte no.
Value [hex]
Description
1
0E
copy of the request
2
80
copy of the request
3 00
4 03
error counter = 0003
hex
= 0003
dec
→
Since the last power-on of the controllere or the reset of the counter, 3 configuration errors
have occurred.
*)
IMPORTANT:
For the query read only the required bytes. Unused bytes can contain information of
previous queries.
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...