DP module 12: Extended command channel
Module 12, extended command 5:
set the operating mode of the AS-i master
9-13
9.9
Module 12, extended command 5:
set the operating mode of the AS-i master
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R R
M
0/1
user ID
command number = 05
hex
= 05
dec
2
reserved = 0
reserved = 0
3
0 0
Mod
4…18
not used
Legend
→
page
and
Mod
set the operating mode of the AS-i master
Mod=0: activate protected mode
Mod=1: activate configuration mode
Example:
Word no.
Value [hex]
Description
1 0105
M=0: AS-i master 1
01 = user ID changes e.g. to 1
05 = command number 5
2 0000
reserved
000
0
activate protected mode
3
000
1
activate configuration mode
Response from controllere (gateway) in the normal case
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0 B=0
M
0/1
reflected user ID
reflected command number = 05
hex
2…18
not changed
Example:
Word no.
Value [hex]
Description
1
0
105
M=0: AS-i master 1
01 = reflected user ID 1
05 = reflected command number 5
2…18 0000
not
changed
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...